A range of Schneider Electric retrofit kits designed to measure the power and energy in existing installations without requiring complete disconnection of cabling. The meters allow data collection using pulsed output, Modbus RS485 and Modbus TCP communications. Due to the meters size and configuration, they can be installed where space is limited. They can also be stacked to allow for multiple meters and an integrated gateway server to be assembled.
• By monitoring power consumption you can identify waste, potential energy saving opportunities and prioritise actions • Can be used In any commercial or industrial application • Standard retrofit kits incorporating MID approved meters can be utilised for energy billing purposes • IP40 protection
Parameters measured:
• Voltage • Current • Frequency • Active power • Reactive power • Power factor • Harmonic distortion
400 (Phase and Neutral) V ac, 690 (Phase) V ac, 9 A, 65 Hz
Measurement Range
10 mA → 9 A, 20 → 400 (Phase and Neutral) V ac, 35 → 690 (Phase) V ac, 45 → 65 Hz
Minimum Measurement
20 (Phase and Neutral) V ac, 35 (Phase) V ac, 10 mA, 45 Hz
Series
PM5000
Approvals
CE Conforming to IEC 61010-1, CULus Conforming to UL 61010-1, EN 50470-1, EN 50470-3, IEC 60529, IEC 61557-12, IEC 62053-22, IEC 62053-24, MID Conforming to EN 50470-1, MID Conforming to EN 50470-3