Eaton 160A British Standard Fuse, B2, 415V ac, 111mm
- RS庫存編號:
- 156-8692
- 製造零件編號:
- DD160
- 製造商:
- Eaton
可享批量折扣
Price 个**
HK$329.00
64 現貨庫存,可於3工作日發貨。*
* 交貨日期可能會根據您選擇的數量和交貨地址而變更。
訂單金額滿 HK$850.00 即可享受 免費 送貨服務
單位 | 每單位 |
---|---|
1 - 24 | HK$329.00 |
25 - 99 | HK$315.90 |
100 + | HK$302.70 |
** 參考價格
- RS庫存編號:
- 156-8692
- 製造零件編號:
- DD160
- 製造商:
- Eaton
豁免
Cooper Bussman Bolted Tag Fuse - British Standard
Cooper Bussman's bolted tag fuse is essentially a fuse that is fitted with brackets, these brackets allow the fuse to be bolted onto a fuse holder. Predominantly, this type of fuse is used within installations as a "weak link". They are designed to break when a fault occurs, such as an overcurrent or short circuit - they are a safety and damage measure. Cooper Bussman's fuses are commonly found within a multitude of industrial applications, electrical equipment and wiring systems.
Features & Benefits
• The low-temperature rise enables the fuse to be suitable for high-density mounting applications
• Fuse links, specifically designed for the protection of applications
• Conforms to industry standards
• Low voltage fuse
• Suitable for three-phase applications
• Suitable for type 2 co-ordinated applications as defined in IEC 947-4
• Low power loss, typically 20% lower than the requirements of BS88
• Fuse links, specifically designed for the protection of applications
• Conforms to industry standards
• Low voltage fuse
• Suitable for three-phase applications
• Suitable for type 2 co-ordinated applications as defined in IEC 947-4
• Low power loss, typically 20% lower than the requirements of BS88
Why use a slotted tag fuse?
A slotted tag fuse is distinguished by the metal slotted tags that extend off the ends of the fuse. This tag can either enable the fuse to have an offset tag or be centred to the fuse. Predominantly, this type of fuse is used within installations as a "weak link". They are designed to break when a fault occurs, such as an overcurrent or short circuit - they are a safety and damage protection measure within electrical circuits.
Eaton British Standard Fuse, B2, 160 A DD160
This low-voltage British Standard fuse from Eaton can be used to protect electrical equipment such as wiring systems and industrial and switchgear applications. It's a bolted tag fuse (also known as an offset slotted fuse), meaning it's fitted with tags that you can use to screw it into a fuse holder or to bolt it directly onto a busbar. This fuse will also mount into a 200DF fuse block. As a gG-type fuse, it's suitable for general-purpose use.
• High rupture capacity means it's able to withstand short-term surges up to 80 kA at 690 V AC without blowing
• B2 fuse size of 47 (body height) x 31 (body diameter) x 136 mm (overall length), which is a British Standard size
• Suitable for protecting the three-phase applications used in most industrial systems
• A power loss that's typically 20% lower than BS 88-standard requirements prevents systems from overheating
• B2 fuse size of 47 (body height) x 31 (body diameter) x 136 mm (overall length), which is a British Standard size
• Suitable for protecting the three-phase applications used in most industrial systems
• A power loss that's typically 20% lower than BS 88-standard requirements prevents systems from overheating
Can I reuse the circuit after the fuse has blown and been replaced?
This fuse is suitable for type-2 coordinated applications as defined in IEC (International Electrotechnical Commission) 947-4, meaning it should blow without significant damage to the starter, so you can still use the application following a short circuit.
Note
Eaton formerly known as Bussmann
Attribute | Value |
---|---|
Current Rating | 160A |
Fuse Size | B2 |
Voltage Rating | 415V ac |
Fuse Standard | BS 88, IEC 269 |
Fixing Centres | 111mm |
Application Category | gG |
Tag Width | 19mm |
High Rupture Capacity | Yes |
Overall Length | 136mm |
Body Diameter | 31mm |
Tag Type | Bolted |
Body Length | 47mm |
Tag Orientation | Centred |
Body Height | 31mm |
Fuse Dimensions | 31 x 47mm |