Eaton xEffect MCB, 1P, 6A Curve C, 240 → 415V AC, 48V DC, 10 kA Breaking Capacity
- RS庫存編號:
- 922-6898
- 製造零件編號:
- 102084 FAZ-C6/1-NA
- 製造商:
- Eaton
單價 个
HK$334.50
46 現貨庫存,可於3工作日發貨。*
* 交貨日期可能會根據您選擇的數量和交貨地址而變更。
訂單金額滿 HK$850.00 即可享受 免費 送貨服務
單位 | 每單位 |
---|---|
1 + | HK$334.50 |
- RS庫存編號:
- 922-6898
- 製造零件編號:
- 102084 FAZ-C6/1-NA
- 製造商:
- Eaton
Eaton FAZ Series MCBs
Eaton FAZ- miniature circuit breakers are Current limiting design provides fast short-circuit interruption that reduces the let-through energy that can damage the circuit, Trip-free design. Breaker cannot be defeated by holding the handle in the ON position
Features and Benefits
Thermal-magnetic overcurrent protection
Power to the circuit breakers can be fed from the line or load side
Clear indication of contact position via front switch toggle
Easy installation on DIN rail. Module width of only 17.5 mm (per pole)
Six levels of short-circuit protection, categorized by B, C, D, K, S and Z curves
Small modular width of the device and accessories saves space in the panel or equipment, which can lead to cost savings
Dual rated for IEC 60947-2 standard
Module widths: 1 Pole 17.5mm, 2 pole 35mm and 3 pole 52.5mm
Power to the circuit breakers can be fed from the line or load side
Clear indication of contact position via front switch toggle
Easy installation on DIN rail. Module width of only 17.5 mm (per pole)
Six levels of short-circuit protection, categorized by B, C, D, K, S and Z curves
Small modular width of the device and accessories saves space in the panel or equipment, which can lead to cost savings
Dual rated for IEC 60947-2 standard
Module widths: 1 Pole 17.5mm, 2 pole 35mm and 3 pole 52.5mm
Standards
IEC 60947-2 Relates to Low Voltage Circuit Breakers for use in industrial and similar
Installations. In the UK traditionally known as moulded case circuit breakers
(MCCBs) and also air circuit breakers (ACBs).
Installations. In the UK traditionally known as moulded case circuit breakers
(MCCBs) and also air circuit breakers (ACBs).
Q: What is the differences in the Tripping Curves B, C, D and S?
A: Curve B: Tripping: 3 to 5 times the rated current.
Applications: protection of generators, persons, very long cables
Curve C: Tripping: 5 to 10 times the rated current
Applications: protection of circuits and general applications
Curve D: Tripping: 10 to 14 times the rated current
Curve S Tripping 13 to 17 times the rated current
Suitable for applications where high levels of inrush current are expected. Instantaneous trip is 13–17X rating of device (In). The high magnetic trip point prevents nuisance tripping in high inductive applications such as motors, transformers and power supplies
Standards
IEC 898; BS/EN60-898; EN50 022/DIN46277-3 (BS5584).
FAZ-C*/* & FAZ-S*/* = IEC/EN60947-2
FAZ-C*/* & FAZ-S*/* = IEC/EN60947-2
Eaton xEffect Mini Circuit Breaker, 6 A, 1 Pole - FAZ Series - FAZ-C6/1-NA
Use this mini circuit breaker (MCB) from Eaton's FAZ series to prevent damage to your electrical circuits due to short circuits and overloads. It's a C-Curve unit, so it will instantaneously trip at five to ten times the rated current of 6 A to ensure safety in the event of a high current surge. The built-in toggle switch makes it simple to reset and clearly indicates the contact position, while the screw terminal contacts allow for easy installation. You can use this type of MCB for a range of lighting and industrial machinery applications.
• Broad AC voltage rating of 240 to 415 V makes it a versatile choice
• Compact dimensions of 17.8 (length) x 65.5 (width) x 80 mm (depth) for use in tight spaces
• Wide operating temperature range of -40°C to +75°C to withstand harsh environmental conditions
• Compact dimensions of 17.8 (length) x 65.5 (width) x 80 mm (depth) for use in tight spaces
• Wide operating temperature range of -40°C to +75°C to withstand harsh environmental conditions
What safety features does this MCB have?
This MCB is finger-proof to prevent electric shocks and also has a trip-free mechanism, meaning it will trip in the presence of a short circuit or overload even if the handle is held in the 'on' position.
Note
Eaton formerly known as Moeller
Attribute | Value |
---|---|
Number of Poles | 1P |
Current Rating | 6A |
Tripping Characteristics | Type C |
Rated AC Voltage | 240 → 415V |
Rated DC Voltage | 48V |
Breaking Capacity at Maximum Voltage Rating | 10 kA |
Range | xEffect |
Circuit Breaker Type | MCB |
Length | 17.8mm |
Width | 66mm |
Mounting Style | DIN Rail Mount |
Depth | 80mm |
Model Number | FAZ-C6/1-NA |
Break Time | Instantaneous |
Tripping Mechanism | Thermal-Magnetic |
Terminal Contact Type | Screw |
Reset Actuator Type | Toggle Switch |