Better World
Schneider Electric Phase, Voltage Monitoring Relay, 3 Phase, SPDT, 183 → 528V ac, DIN Rail
- RS庫存編號:
- 146-597
- 製造零件編號:
- RM17TU00
- 製造商:
- Schneider Electric
Price 个**
原價 HK$1,416.44
您付款
HK$1,229.00
12 現貨庫存,可於3工作日發貨。*
* 交貨日期可能會根據您選擇的數量和交貨地址而變更。
訂單金額滿 HK$850.00 即可享受 免費 送貨服務
單位 | 每單位 |
---|---|
1 + | HK$1,229.00 |
** 參考價格
Better World
我們的 Better World 產品系列可讓您輕鬆選擇值得信賴的環保產品。 點擊此處了解更多。
- RS庫存編號:
- 146-597
- 製造零件編號:
- RM17TU00
- 製造商:
- Schneider Electric
- COO (Country of Origin):
- ID
RM17 Tx00 Series Three-Phase Network Control Relay
Schneider Electric RM17Tx00 Series multi-function 3 phase supply control relays. Monitoring the correct sequencing of phases L1, L2, and L3 and the total loss of one or more of each phase. In the event of a phase sequence or missing phase fault, the relay opens instantly. In the event of voltage fault, the relay opens at the end of the time delay set.
Clear hinged front cover
Front face potentiometer
LED output status
DIN rail
Front face potentiometer
LED output status
DIN rail
Phase, Asymmetry and Under-Voltage / Over-Voltage Controller: RM17 TE00
The relay monitors its own Un supply voltage:
The relay controls: the direct sequence of the three phases, the loss of at least one of the three phases (U measured < 0.7 x Un), asymmetry adjustable from 5 → 15 % of Un, over- and under-voltage drift in window mode adjustable from 2 → 20 % of Un.
The relay controls: the direct sequence of the three phases, the loss of at least one of the three phases (U measured < 0.7 x Un), asymmetry adjustable from 5 → 15 % of Un, over- and under-voltage drift in window mode adjustable from 2 → 20 % of Un.
Standards
NF EN 60255-6 and IEC 60255-6
Approvals
UL, CSA, GL, C-Tick, GOST
Schneider Electric Harmony Control Series Monitoring Relay, SPDT Contact Configuration, Phase/Voltage Monitoring Application - RM17TU00
This monitoring relay is tailored for effective phase voltage supervision and electrical phase management across diverse applications. It delivers essential undervoltage protection, ensuring that systems function within specified voltage parameters. Its robust design contributes to enhanced operational efficiency and safety in electrical systems.
Features & Benefits
• Monitors voltage levels from 183 to 528VAC for broad compatibility
• Adjustable time delay from 0.1 to 10s for customised responses
• SPDT configuration provides versatility in signal management
• Compact DIN rail relay optimises installation space
• Incorporates phase failure and sequence detection for improved system reliability
• Self-extinguishing housing enhances durability in demanding environments
• Adjustable time delay from 0.1 to 10s for customised responses
• SPDT configuration provides versatility in signal management
• Compact DIN rail relay optimises installation space
• Incorporates phase failure and sequence detection for improved system reliability
• Self-extinguishing housing enhances durability in demanding environments
Applications
• Utilised for phase voltage monitoring in industrial machinery
• Employed in automation systems requiring voltage sensing
• Provides undervoltage protection in electrical cabinets
• Suitable for electrical phase monitoring in power distribution networks
• Employed in automation systems requiring voltage sensing
• Provides undervoltage protection in electrical cabinets
• Suitable for electrical phase monitoring in power distribution networks
What is the installation process for this relay?
The relay can be mounted on a standard DIN rail, requiring only screw terminal connections for quick setup.
How does the time delay function enhance operation?
The time delay feature allows for adjustable settings, preventing unnecessary tripping during transient voltage drops.
Is it suitable for varying electrical environments?
Yes, it operates effectively within a wide temperature range and is designed for both industrial and commercial applications.
Can it be integrated into existing electrical systems?
The relay is compatible with common electrical setups and can be incorporated without extensive modifications.
What maintenance is required for optimal performance?
Regular inspections are advised to ensure terminals are secure and clean, although the device is designed for minimal upkeep.
Schneider Electric Voltage, Current, Phase & Motor Protection
Attribute | Value |
---|---|
Monitoring Application | Phase, Voltage |
Electrical Phase | 3 |
Voltage Sensing Range | 183 → 528V ac |
Contact Configuration | SPDT |
Voltage Sensitivity | Undervoltage |
Mounting Type | DIN Rail |
Phase Sensitivity | Phase Failure, Phase Sequence |
Time Delay | 0.1 → 10s |
Series | Harmony Control |
Better World Verification | Green Premium |
Better World Product | Yes |
Length | 72mm |
Standards Met | CE, CSA, UL |
Special Features | IP20 Terminals |
Width | 17.5mm |
Dimensions | 72 x 17.5 x 90mm |
Terminal Type | Screw |
Operating Temperature Range | -20 → +50°C |
Height | 90mm |
Minimum Voltage Sensed | 183V ac |
Minimum Operating Temperature | -20°C |
Maximum Operating Temperature | +50°C |
Maximum Voltage Sensed | 528V ac |