Dold Phase Monitoring Relay, 3 Phase, DPDT, DIN Rail

小計(1 件)*

HK$1,664.20

Add to Basket
選擇或輸入數量
有庫存
  • 16 件準備從其他地點送貨
**需要更多嗎?**輸入您需要的數量,然後按一下「查看送貨日期」以查詢更多庫存和送貨詳細資訊。
單位
每單位
1 +HK$1,664.20

* 參考價格

RS庫存編號:
240-8923
製造零件編號:
BA9041 3AC50Hz 400V
製造商:
Dold
透過選取一個或多個屬性來查找類似產品。
選取全部

品牌

Dold

Monitoring Application

Phase

Electrical Phase

3

Contact Configuration

DPDT

Mounting Type

DIN Rail

Phase Sensitivity

Phase Sequence

Time Delay

<50ms

Series

BA 9041

Length

119.8mm

Minimum Operating Temperature

-20°C

Maximum Operating Temperature

+60°C

Operating Temperature Range

+60°C

Dimensions

119.8 x 45 x 73.2mm

Height

73.2mm

Width

45mm

COO (Country of Origin):
MT

Phase sequence relay, BA9041


Detects phase sequence errors and phase failure
with 2 changeovers
Overall width 45 mm

The BA9041 can recognise the phase sequence L1 - L2 - L3 of a three-phase network and therefore avoid an incorrect rotational direction.
The BA9041 phase sequence relay monitors the presence of the 3 phase voltages in a three-phase network in addition to the maintenance of the correct phase sequence. If all 3 phase voltages are present at the device in the correct phase sequence, the output contacts change over from the initial position to the operative position, contacts 11-14 and 21-24 are closed, and a green LED lights up.
If the voltage falls below 60 % UN in one phase, the relay is de-energised (in accordance with: IEC 255, VDE 0435).


Phase Sequence/Failure Relays


Monitoring of 3 phase supplies
Orange housing manufactured to DIN 43 880
DIN rail mount