Broyce Control Phase, Voltage Monitoring Relay, 3 Phase, SPDT, 243 → 540V ac, DIN Rail
- RS庫存編號:
- 135-6181
- 製造零件編號:
- LPRC/2 400V
- 製造商:
- Broyce Control
47 現貨庫存,可於3工作日發貨。
單價 个
HK$1,243.77
單位 | 每單位 |
---|---|
1 + | HK$1,243.77 |
- RS庫存編號:
- 135-6181
- 製造零件編號:
- LPRC/2 400V
- 製造商:
- Broyce Control
- COO (Country of Origin):
- GB
LPRC/2 Phase Failure, Phase Sequence, Under and Over Voltage plus Time Delay
Broyce Controls L-Series signal conditioners use a QR barcode marking method allowing direct access to all technical data sheets, ensuring correct information is always at your finger tips!
Features and Benefits
Compact 17.5 mm DIN Rail housing
Microprocessor based
True R.M.S. monitoring measuring phase to phase (three wire) or phase to neutral (4-wire) voltages
Selectable nominal voltages to suit most popular three wire or 4-wire supply voltages
Monitors own supply and detects if one or more phases exceed the set Under or Over voltage trip levels
Detects incorrect phase sequence, phase loss and neutral loss1
Adjustments for Under and Over voltage trip levels
Adjustment for time delay
Independent relay outputs - Under voltage monitoring / Over voltage monitoring
2 x SPDT relay output 5A
Green LED indication for supply status
Individual Red LED indication for both relay statuses
Approvals
UL Certification
Broyce Monitor Relays
Note
Output relay contact rating specified at 250Vac
Attribute | Value |
---|---|
Monitoring Application | Phase, Voltage |
Electrical Phase | 3 |
Voltage Sensing Range | 243 → 540V ac |
Contact Configuration | SPDT |
Voltage Sensitivity | Overvoltage, Undervoltage |
Mounting Type | DIN Rail |
Phase Sensitivity | Phase Failure, Phase Sequence |
Time Delay | 0.2 → 10s |
Series | L |
Width | 17.5mm |
Height | 89mm |
Minimum Operating Temperature | -20°C |
Length | 66.5mm |
Dimensions | 66.5 x 17.5 x 89mm |
Operating Temperature Range | +60°C |
Terminal Type | Screw |
Maximum Operating Temperature | +60°C |
Special Features | Microprocessor Based, Detects Incorrect Phase Sequence, Phase Loss And Neutral Loss, Adjustments For Under And Over Voltage Trip Levels, Adjustment For Time Delay |
Maximum Voltage Sensed | 540V |
Number of Poles | 2 |