Fluke 1664FC Multifunction Tester 1000 V Earth Resistance Measurement With USB

小計(1 件)*

HK$22,018.65

Add to Basket
選擇或輸入數量
有庫存
  • 3 件準備從其他地點送貨
**需要更多嗎?**輸入您需要的數量,然後按一下「查看送貨日期」以查詢更多庫存和送貨詳細資訊。
單位
每單位
1 +HK$22,018.65

* 參考價格

RS庫存編號:
117-6667
Distrelec 貨號:
300-60-476
製造零件編號:
FLK-1664FC SCH
製造商:
Fluke
透過選取一個或多個屬性來查找類似產品。
選取全部

品牌

Fluke

Loop Impedance Test Type

Phase to Neutral, Phase to Earth

Product Type

Multifunction Tester

Automatic RCD Test

Yes

RCD Ramp Test

Yes

Model Number

1664FC

Maximum Voltage Measurement

500V ac/dc

Earth Resistance Measurement

Yes

Downloadable Data

Yes

Interface Type

USB

Continuity Test Current

10mA

RCD Test Type

Type S, Type G, AC

Remote Switch Mode

Yes

Weight

1.3kg

Length

100mm

Standards/Approvals

CSA, UL 61010, ANSI/ISAs82.02.01 2000, CE, EN 610101 Ed 2.0 (200102)

Height

125mm

Test Standards

EN 61557-1, EN 61557-7, EN 61557-10

IP Rating

IP40

Safety Category Voltage

500V

Power Source

Battery

Safety Category Level

CAT III, CAT IV

Maximum Operating Temperature

40°C

Display Type

LCD

Minimum Operating Temperature

-10°C

Battery Type

AA

豁免

COO (Country of Origin):
GB

Fluke Multifunction Tester, 500V Maximum Voltage Measurement, 1000V Insulation Test Voltage - FLK-1664FC SCH


This multifunction tester is a portable instrument for verifying electrical installations and protective devices across industrial and commercial environments. It combines insulation, continuity, loop impedance and RCD testing with live data transfer to mobile devices, enabling on-site measurement capture and reporting while working to national installation practices.

Features & Benefits


• Insulation test up to 1000V protects connected equipment from damage
• Continuity test current of 1 mA allows safe motor winding checks
• Loop impedance phase to NEUTRAL tester provides Rapid ZI and PSC readings
• RCD ramp test meter Fluke supports VAR mode for EV/DC RCDs
• Earth resistance measurement tester outputs 25V at 128 Hz for RE checks
• Downloadable data USB tester syncs results to smartphone/cloud

Applications


• Suitable for commissioning domestic and commercial distribution boards
• Ideal for testing EV charging DC protection and 6 mA monitors
• Used for maintenance diagnostics on motor windings and circuits
• Can be used for field data collection and report generation via cloud
• Used with site acceptance procedures requiring RCD trip and timing checks

What power source does it use and how many cells are required?


It runs on six AA batteries, enabling field use without mains power.

Which overvoltage categories does it meet for safe measurement environments?


It is rated for CAT III at 500V and CAT IV at 300V for site testing.

How does it handle non‑trip RCD loop tests for Faster readings?


It offers a high‑current loop mode and a Z‑max memory to capture Peak loop values without tripping protective devices.

Can it measure prospective fault current and how is that calculated?


It computes PEFC or PSC by dividing measured mains voltage by loop or line resistance and displays the Value in amps.

What interfaces are available for exporting results and remote control?


It includes a USB Interface for data download and a remote probe/lead for switch‑mode operation.