Jumo Jumo TYA-200 DIN Rail, DIN Rail Power Controller

小計(1 件)*

HK$8,008.12

Add to Basket
選擇或輸入數量
暫時缺貨
  • 2 件從 2026年3月27日 起裝運發貨
**需要更多嗎?**輸入您需要的數量,然後按一下「查看送貨日期」以查詢更多庫存和送貨詳細資訊。
單位
每單位
1 +HK$8,008.12

* 參考價格

RS庫存編號:
793-4039
Distrelec 貨號:
301-42-415
製造零件編號:
709061/8-01-020-001-230-00/252
製造商:
Jumo
透過選取一個或多個屬性來查找類似產品。
選取全部

品牌

Jumo

Product Type

Power Controller

Maximum Current

250A

Maximum Operating Temperature

45°C

Minimum Operating Temperature

0°C

Energy measurement

Yes

Diagnostics

Integrated Diagnostic

Digital Comms

PROFIBUS-DP, RS422 (Modbus RTU), RS485

Firing Mode

Burst Fire, Phase Angle Operation

Maximum Voltage

500V

Display Type

LCD

Length

155mm

Standards/Approvals

No

IP Rating

IP20

Width

45 mm

Series

Jumo TYA-200

Mount Type

DIN Rail, DIN Rail

COO (Country of Origin):
DE

TYA-201 1-Phase Power Controller


The micro-processor controlled single-phase power controller Jumo TYA 201 displays all parameters in a backlighted LCD display and is operated using the 4 keys on the front.

SCR power controllers are employed where larger resistive and inductive loads have to be switched, e.g. in industrial kiln construction and in plastics processing. The SCR power controller comprises two SCRs connected in anti-parallel, the insulated cooling body and the control electronics.

The operating modes are phase-angle, burst-firing mode, half-wave control, SSR logical operation , fast logical operation, alpha start and soft start.

Available subordinate controls are U, U2, I, I2 and P control.

Use of a subordinate control ensures that fluctuations in the supply voltage do not affect the control loop during the control process.

Single-phase SCR power controller

Simple configuration of the device through plain text display

Setup program for configuration via USB interface

Transmission of the setup data is possible even without voltage supply to the device (USB port supplies power)

Network load optimization through dual energy management

Generalized phase mode, burst-firing mode, and half-wave control

Soft start function

Current limiting

Resistance monitoring and limitation for MoSi2 heating elements

Teach-in function for the detection of partial load failure

Integrated diagnostic systems (e.g. rotating field detection)